CT17-I and CT17-II type spring operating mechanism

General

CT17-I and CT17-II type spring operating mechanisms are available for operating 10kV, 20KA, ,25kA and 31.5kA series indoor VCB, which are adopted the unilateral hanging type spring configuration with the function of energy stored by power or by manual, CO operation respectively by power and manual and over current protected. They are widely used for varies kinds of VCB, especially suitable for ZN13, ZN28 and ZN 38 series, and characterized by small dimension, low noise and long mechanical life (above 10000 operations cycles).
Overall dimension (H*W*D): 400*440*140(mm)
Weight:? about 23kg.

Main Technical Data:

No.?

Item

Data?

1

Closing power

70~150J

2

Rated power of motor

70~120W

3

Contact at frequent CO of travel switch

2 pairs

4

Contact at frequent CO of auxiliary switch

6 pairs

5

Rated voltage of motor

AC/DC 110V, AC/DC 220V

6

Output turning angle of mechanism

400~500

7

Energy-stored duration

=15secs

8

Mechanical life

10000 cycles


CT17S and CT17G Spring Operating Mechanism

General description

CT17S type spring operating mechanisms are available for operating 10kV, 20KA, 25kA, 31.5kA and 40kA series indoor VCB, they are adopted the bilateral hanging type spring configuration with the function of energy stored respectively by power or by manual. And it can be equipped with three overcurrent protectors and one undervoltage protector. With the good property and convenient maintenance, especially suitable for ZN13, ZN28 and ZN 38 series VCB.
Overall dimension (H*W*D): 418*360*150(mm)
Weight: about 26kg.

CT17G type spring operating mechanism is in compliance with fixed switchgear; it is also adopted bilateral hanging spring type configuration.
Switching capacity is 20kA~40kA.
Overall dimension: (H*W*D): 450*335*150(mm)

Main Technical Data

No.

Item

Data

1

Closing power

70~150J

2

Rated power of motor

70~120W

3

Contact at frequent CO of travel switch

2 pairs

4

Contact at frequent CO of auxiliary switch

6 pairs

5

Rated voltage of motor

AC/DC 110V, AC/DC 220V

6

Output turning angle of mechanism

400~500

7

Energy-stored duration

=15secs

8

Mechanical life

10000 operation cycles

 
___________________________________________________________________________________
   

Sunway Hanguang Electric Manufacturing Inc.
Copyright 2004-2007 Sunway Hanguang Company. All right reserved.

TEL: 0086-712-2914953 FAX: 0086-712-2681513 SiteMap Links
MSN:lxgzjn@hotmail.com

E-Mail:webmaster@swhge.com
H t t p : / / w w w . s w h g e . c o m